Sign In | Join Free | My burrillandco.com
Home > Plug In Bushing >

Fully Shielded GIS Plug In Bushing Termination Kits 35KV 1250A Indoor

    Buy cheap Fully Shielded GIS Plug In Bushing Termination Kits 35KV 1250A Indoor from wholesalers
     
    Buy cheap Fully Shielded GIS Plug In Bushing Termination Kits 35KV 1250A Indoor from wholesalers
    • Buy cheap Fully Shielded GIS Plug In Bushing Termination Kits 35KV 1250A Indoor from wholesalers

    Fully Shielded GIS Plug In Bushing Termination Kits 35KV 1250A Indoor

    Ask Lasest Price
    Brand Name : Chuangyin
    Model Number : Plug-in Bushing 4#
    Certification : Test Report
    Price : negotiable
    Payment Terms : L/C, D/A, D/P, T/T, Western Union, MoneyGram
    Supply Ability : 36,000,00pcs per year
    Delivery Time : Within 7 days
    • Product Details
    • Company Profile

    Fully Shielded GIS Plug In Bushing Termination Kits 35KV 1250A Indoor


    42KV 800A /1250A Indoor Epoxy Resin Cast Bushing GIS Bushing IEC


    1. Introduction:


    Plug-in Termination Kits is suitable for GIS incoming and outgoing wire connection. It is designed to mate with epoxy insulated bushing, and connect wire to switchgear fully shielded, fully insulated, fully sealed. Your technician can install, repair or maintain equipment and power cable system without undermining seal between bushing and GIS.
    Meets the standard of EN50180-50181 interface type 2#,


    2.Packing:


    Termination housing

    Locking halves

    Protection cover

    Cable Sheath Braided Ground Wire

    CFS

    Wipers
    Installation instruction

    Silicone Grease

    Certificate


    3.Structure:


    1.Epoxy Insulated Bushing

    2.Locking Halves

    3. Stress Relief Cone

    4. Plug-in termination kit

    5. Protection cover

    6. pressure spring

    7. Cable sheath

    8. Grounding Wire

    9. Cable Cable not included


    4. Parameters:


    Part number2#3#
    Voltage ratings35kV35kV
    Rated current800A1250A
    AC withstand voltage 5 min117kV117kV
    DC withstand voltage 15 min104kV104kV
    PD at ambient temperature45kV10pC45kV10pC

    Impulse voltage at elevated

    temperature

    200kV200kV
    Cross section50 〜240mm250 〜630mm2

    5. Selection Table:


    Part No.3#
    DimensionsL1mm147.5
    L2mm216
    <pDmm55
    InstallationBushing position 1mm113
    n6
    22mm130
    N3

    Model Option:

    ModelPart No.
    Plug-in Bushing 4#CYS-NC-4